actiVAR - MOTOR START CALCULATOR

The following calculator computes the expected performance of NEPSI's actiVAR in reducing voltage sags associated with large motor starts. Expected voltage sag and voltage drop are calculated for "across-the-line motor starts" based on system impedance data and motor nameplate ratings.

Calculator-1


Known variables:

Source Data: Source Voltage, Source Short Circuit Level, and X/R ratio

Supply Side Transformer Data: Transformer Power Rating (MVA), leakage impedance (in % on transformer base), and X/R ratio of leakage impedance

Motor Nameplate Data: Motor Voltage rating, motor full load current (FLA), motor locked rotor current (see code letters following calculator if not known), locked rotor power factor (assume 20% if not known)

Unknown Variables: Voltage drop and voltage sag at motor and supply transformer primary

--------SOURCE DATA--------    
SOURCE VOLTAGE (Kv LINE-TO-LINE): CALCULATED        
SOURCE 3-PHASE SHORT CIRCUIT CURRENT (kA): Rpu Xpu        
X/R RATIO:        
--------TRANSFORMER DATA--------        
MVA RATING: CALCULATED        
PERCENT IMPEDANCE (ON TRANSFORMER BASE): Rpu Xpu        
X/R RATIO:        
--------MOTOR DATA--------        
MOTOR VOLTAGE RATING (kV): CALCULATED        
FULL LOAD CURRENT RATING (FLA):        
LOCK ROTOR CURRENT (%):        
LOCK ROTOR PF (%): Rpu Xpu        
MOTOR KVA BASE RATING:        
--------actiVAR DATA-------- CAP/MOT EQIV.    
actiVAR RATING (kV LINE-TO-LINE): Rpu Xpu Rpu Xpu    
actiVAR RATING (MVAR): 0.00    
actiVAR PERFORMANCE    
  VMOTOR VPRIMARY TORQUE LOSS FROM VOLTAGE SAG (%) actiVAR TORQUE ADVANTAGE (%)    
  VOLTAGE DROP (%) VOLTAGE SAG (%) VOLTAGE DROP (%) VOLTAGE SAG (%)    
WITHOUT actiVAR    
WITH actiVAR    
Motor Inrush Current    
Inrush Current with actiVAR amps Per Unit of FLA      
Inrush Current without actiVAR amps Per Unit of FLA      
   
     
Use Locked-Rotor CODE on Nameplate (KVA/HP) to determine Locked Rotor Current (%)      
                 
       
Screen Clipping
   
Enter KVA/HP Based on Table 1:        
HP Rating of Motor (HP):        
Enter Motor Terminal Voltage (kV):        
Enter FLA rating of Motor (Amps):        
           
Motor Inrush Current: amps      
Locked Rotor Current %:        
     
     
actiVAR Voltage Resolution, Stage Sequence, Step & Stage Size Table      
                 
System Voltage: kV            
Total kvar required by actiVAR: kvar            
Calculated MVAsc at actiVAR: MVA            
                 
                 
Number of Steps Number of Stages Stage Sequence Smallest Step Size Required Valve Rating of Largest Stage (amps)* Approximate Voltage Resolution `  
1 1 1  
2 2 1:1  
3 2 1:2  
3 3 1:1:1  
5 3 1:2:2  
6 3 1:2:3  
7 3 1:2:4  
4 4 1:1:1:1  
7 4 1:2:2:2  
9 4 1:2:3:3  
11 4 1:2:4:4  
15 4 1:2:4:8  
               
* Transient Current Rating of Delta Valve: ≈ 500 Amps. Table is based on Delta Connected TSC.        

Basis of Calculation



This calculator provides the initial voltage drop and voltage sag at the motor terminals and at the primary side of the supply transformer based on source impedance data and motor nameplate data. All impedance data is converted to per unit impedance values on the motor's base KVA rating (these values are shown in the calculator). Motor impedance data is determined based on the locked rotor current and starting power factor. This information is available on the motor data sheets or can be obtained from the motor code letter provided on the nameplate of the motor (use the table to determine locked rotor current based on motor code letter).

A voltage divider is used to calculate the expected voltage at the motor and at the transformer primary. The calculator does not account for dynamic effects of adjacent motors and generators.

Use this calculator to obtain the approximate actiVAR MVAR rating required to meet your performance requirements. Generally, the actiVAR will need multiple steps to meet performance requirements during turn off as the motor accelerates to rated speed.

Code Letter for Locked Rotor Current
(kVA/HP ~ Per Unit Full Load Amps)
Code LetterPer Unit MultiplierCode LetterPer Unit MultiplierCode LetterPer Unit Multiplier
A0.00 - 3.14H6.30 - 7.09R14.00 - 15.99
B3.15 - 3.54J7.10 - 7.99S16.00 - 17.99
C3.55 - 3.99K8.00 - 8.99T18.00 - 19.99
D4.00 - 4.49L9.00 - 9.99U20.00 - 22.39
E4.50 - 4.99M10.00 - 11.19V22.40 AND UP
F5.00 - 5.59N11.20 - 12.47
G5.60 - 6.29P12.50 - 13.99


Of Interest...



A starting motor appears as a large load with very poor power factor, which improves as the motor approaches full speed. Depending on the motor, this may take from two seconds to one minute. The effects from these starts may be reduced in the following ways:

  1. By starting the offending motors during noncritical periods
  2. By not turning them off as often and thus not having to start them as often
  3. Using reduced-voltage starters (RVSS, RAVT auto-transformer)
  4. Using low distortion variable speed drive (VSD)
  5. Using the actiVAR

All electric power utilities set specific limits on the allowable voltage sag during motor starting at the point of common coupling (PCC). These limits are set regardless of the projected plant conditions or loading profiles and are enforced to insure the quality of power distribution grid and to minimize complaints from other customers supplied from the same distribution network.

Utility Limit



The figure below provides a typical chart showing voltage sag limits that may be required by a serving utility. The chart shows a voltage sag limit of 4% or 6% for 1 to 6 fluctuations per day depending upon the time of day. These sag limits would typically be applied at the point of common coupling (PCC) and will vary with each utility. Check with your utility to obtain your limits.



Facility Limit



In general, commercial and industrial customers are allowed as much self-induced voltage sags and voltage flicker as they can tolerate, as long as they do not impact other customers. Voltage sags and flicker can be greater than limits allowed by the local utility at the PCC. The allowable limits are based on the sensitivity of the load and will vary from site to site and with type of load.

As a guideline in identifying potential problems at your facility, Table 1 below indicates the sensitivities of some common devices to voltage sags and voltage flicker.