NEPSI

The Most Trusted Name in Power Factor Correction and Harmonic Filtering

CAPACITORS


Share this product page:   

NEPSI's Metal-Enclosed Harmonic Filter Banks come equipped with individually fused single-phase double-bushing capacitors (internally fused capacitors are provided on request). The capacitors are rated for harmonic filter duty and are normally connected in an ungrounded-wye or split-ungrounded-wye configuration, but can be connected in a grounded-wye or delta configuration for technical or preferential reasons.

All Capacitors contain an internal discharge resistor to reduce the stored voltage to 50 volts or less within 5 minutes from disconnection.

The capacitors have a low loss, non-PCB, all film design that meet or exceeds IEEE, IEC, and ANSI standards.

NEPSI utilizes capacitors from one of three North American suppliers, ABB, GE, or Cooper Power Systems, based upon quality, price, lead-time, and availability at time of order. Specific request for a particular supplier are honored.


The capacitors's kvar rating is based on tuning point requirements and kvar output requirements for the harmonic filter. Voltage ratings are increased for harmonic filter duty with the following considerations:

  1. Maximum expected harmonic filter current. Peaks of individual harmomics are assumed to be 100% coincident.
  2. Nominal system over-voltage of 5%
  3. Ambient voltage distortion equal to the limits set forth by IEEE 519 (at the PCC) or values obtained during measurement
  4. Adherence to IEEE/ANSI maximum continuous operating values:
    1. 110% of rated RMS voltage
    2. 120% of rated peak voltage, i.e. peak voltage not exceeding 1.2 x (square root of two or 1.414) x rated rms voltage, including harmonics, but excluding transients (harmonic currents are 100% coincident).
    3. 135% of nominal RMS current based on rated kvar and rated voltage.
    4. 135% of rated kvar


Click on the cutsheets below for further details.

TYPICAL CAPACITOR SPECIFICATIONS


Externally Fused Units50 to 600 kvar in voltages from 2.4 kV through 24.94 kV
Internally Fused Units200 kvar to 1000 kvar in voltages from 2.4 kV through 12.47kV
BIL Ratings95, 125, 150, and 200kV BIL
Frequency50Hz or 60Hz
DielectricPolypropylene
Impregnation FluidNon-PCB
Discharge ResistorsInternal, will discharge to 50 volts within 5 minutes
StandardsNEMA CP1, IEEE 18, IEC 871, or CSA C155
Case MaterialStainless Steel
Maximum Current135% of Rating (RMS)
Maximum kvar Output135% of Rating (RMS)
Capacitor Tolerance0 to +10%
Maximum Altitude1,000 Meters (without de-rating)
Paint ColorANSI 70 Gray
BushingsWet-process Glaxed Porcelain
Dielectric Losses0.07 Watts/kvar
VARIABLE CAPACITOR SPECIFICATIONS


STANDARD-DUTY
(SD)

HEAVY-DUTY
(HD)

EXTREME-DUTY
(XD)

CONTINUOUS RMS OVERVOLTAGE

110% of rated voltage125% of rated voltage125% of rated voltage

PEAK OVERVOLTAGE

120% of rated voltage135% of rated voltage135% of rated voltage

MAX FAULT CURRENT HANDLING

10,000A10,000A15,000A

AMBIENT OPERATING TEMPERATURE

-40°C - +55°C-40°C - +55°C-50°C - +55°C
PRODUCT LITERATURE


SUPPLIER

FUSING

CUTSHEETS

INSTRUCTIONS

CASE
RUPTURE CURVE

MSDS
DATA SHEETS

Cooper Power Systems External
Cooper Power Systems Internal N/A N/A
General Electric External

Follow us on social media for up-to-date news, videos, and other information: